Products - Ultron (> 20 kVA) - Delta EMEA

DPM Gen2 Series 250-1750 kVA

Uplevel Performance, Ensure Protection

Selected by leading global cloud providers, Delta’s DPM Gen2 introduces advanced features for enhanced efficiency and reliability. This includes OPEX savings with up to 97.3% AC-AC efficiency and improved grid stability. Synchronized Multiple Bus (SMB) and parallel scalability ensures flawless reliability, making it the ideal solution for fortified hyperscale data centers.



 


 


Downloads (EN) Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

OPEX Savings

  • AC-AC efficiency up to 97.3%, efficiency optimization at light loads saves energy costs
  • Clean mode (voltage independent mode) up to 99% efficient guarantees the optimum power condition while maintaining the highest level of efficiency
  • Optimizes energy cost with off-peak charging, avoiding peak-time expense
  • Elevates grid stability through responsive demand reduction and fast frequency regulation, triggers upon utility requests for eligible bill subsidies
 

Impeccable Reliability

  • Assures smooth power transitions with integrated Synchronized Multiple Bus (SMB), minimizing transformer inrush currents and maintaining balanced power from dual sources
  • Parallels up to 8 units for redundancy or expansion, supported by N+1 internal redundancy in power modular configuration
  • Maximizes UPS performance and lifespan with self-diagnosis and key component analysis
 

Ultimate Availability

  • Lithium-ion battery ready. Adjustable battery charging voltage adapts to multiple types of batteries
  • Seamless power shifts to generator with an advance power walk-in function, pausing during frequency issues for smooth transitions without unnecessary generator sizing expansion
  • Grid interactive application. Provides corrective operation for unstable renewal energy sources with an innovative topology design that handles grid and battery power at the same time
  • Easy mounting/cabling that supports both top and bottom cable entry and full front access
 
Applications

UPS EH Series applications

Specifications
  1. Model
  2. DPM-250K / DPM-500K(1) / DPM-750K(1) / DPM-1000K / DPM-1250K / DPM-1500K(1) / DPM-1750K(1)

  3. Power Rating
  4. DPM-250K: 250 kVA / 250 kW
    DPM-500K: 500 kVA / 500 kW
    DPM-750K: 750 kVA / 750 kW
    DPM-1000K: 1000 kVA / 1000 kW
    DPM-1250K: 1250 kVA / 1250 kW
    DPM-1500K: 1500 kVA / 1500 kW
    DPM-1750K: 1750 kVA / 1750 kW
  5. Parallel Configuration: Up to 8 units

  6. Input
  7. Nominal Voltage: 380/ 400/ 415 Vac, 3P3W+PE or 3P4W+PE
  8. Voltage Range: 323-477 Vac (100% load)
  9. Frequency Range: 40-70 Hz
  10. Total Harmonic Distortion (THDi): < 3% (100% resistive load)
  11. Power Factor: > 0.99 (100% load)
  12. Short Circuit Withstand Rating
    DPM-250-750K: 65 kA
    DPM-1000-1750K: 100 kA
  13. Connection: Single or dual feed

  14. Output
  15. Nominal Voltage: 380/ 400/ 415 Vac, 3P3W+PE or 3P4W+PE
  16. Voltage Regulation: ±1% (static)
  17. Frequency: 50/60 ± 0.05 Hz
  18. Total Harmonic Distortion (THDv): < 1% (linear load)
  19. Power Factor: 1
  20. Overload Capability: < 110%: continues, 110-125%: 10 mins, 126-150%: 1 min, > 150%: 1 sec
  21. Current Crest Ratio: 3:1

  22. Efficiency
  23. Online Mode: Up to 97.3%
  24. Clean Mode (VI): Up to 99%

  25. Battery
  26. Battery Type: VRLA, Vented lead-acid, Lithium-ion, Ni-Zinc
  27. Nominal Voltage: 480 Vdc
  28. Quantity: 34-35(2), 36-46 pcs (VRLA 12 V)
  29. Charge Current
    DPM-250K: 125 A
    DPM-500K: 250 A
    DPM-750K: 375 A
    DPM-1000K: 500 A
    DPM-1250K: 625 A
    DPM-1500K: 750 A
    DPM-1750K: 875 A
  30. Protection Design: Battery shunt trip x1, Battery temperature detection x4, Battery breaker status dry contact x1

  31. Communication Interfaces
  32. Display: 10-inch color touchscreen
  33. Port: Smart slot x2, Modbus (RS-485) port x1, REPO port x1, Input dry contact x6, Output dry contact x6, Synchronized Multiple Bus (SMB) x2, Breaker status detection x4, EMS/Console port x1, Ethernet x1
  34. Remote Emergency Power Off (REPO): Optional
  35. Protocols: SNMP, Modbus RTU, Modbus TCP/IP, HTTP(S), SNTP, SMTP, BOOTP, DHCP

  36. Physical
  37. Dimensions (W x D x H) 
    DPM-250K: 1030 x 990 x 2000 mm
    DPM-1000K: 3070 x 990 x 2000 mm
    DPM-1250K:3400 x 990 x 2000 mm
  38. Net Weight
    DPM-250K: 676 kg
    DPM-1000K: 2,408 kg
    DPM-1250K: 2,779 kg

  39. Environment
  40. Operating Temperature: 0 to 40 °C
  41. Humidity: 0-95% (non-condensing)
  42. Audible Noise 
    DPM-250K: < 78 dBA
    DPM-1000K: < 84 dBA
    DPM-1250K: < 85 dBA
  43. Altitude: 0-2,000 m (derating 1%/100m from 1,001-2,000 m)
  44. Storage Temperature: -25 to 70 °C
  45. Ingress Protection: IP20

  46. Conformance
  47. Safety: IEC 62040-1, CE
  48. EMC: IEC 62040-2
  49. Performance: IEC 62040-3
  50. Sustainability: RoHS, REACH, Energy Star

  51. Features
  52. Standard
    Advance Power Walk-in for Generator
    Backfeed Protection with Contactor
    Burn-in Test without Load Bank
    Cold Start Function
    Synchronized Multiple Bus (SMB)
    Frequency Conversion
    Battery Shunt Trip
    Auxiliary Power 48 Vdc for Shunt Trip
  53. Optional
    Advance Failure Prediction
    Grid Interactive
    Software Integration with Delta Lithium Battery BMS
    DC Battery Ground Fault Detector
    Integrated Battery Switch Cabinet
    IR Scan Window

  54. (1) Upcoming product
    (2) 34-35 pcs require service setting and load derating
  55. All specifications are subject to change without prior notice.