Products - Ultron (> 20 kVA) - Delta EMEA

HPH Gen2 Series 20/30/40 kVA

Combines reliable protection, cost-effective power, compact footprint and high-level performance

The latest HPH Gen2 20-40 kVA UPS offers a best in class footprint and high-level performance. With advanced technology and thermal management, it achieves the world’s leading power density and promises 40°C without de-rating. The 0.99 input PF and iTHD < 2% ensure maximum upstream source compatibility. Low total cost of ownership is achieved by > 96% efficiency, energy recycle mode, wider battery quantity configuration and inbuilt 15 A charger. In addition, it provides a user-friendly interface touch panel, manual protection devices and caster wheels for easy deployment, installation and operation. All these features provide the ideal solution for various small and medium-sized data centers and critical power backups.

HPH Gen.2 series UPS 20-40kVA - features
 


 
 


Downloads:
English French German Polish
Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Easy Deployment and Maintenance with Compact Design

  • Inbuilt casters for easy move-in, positioning and maintenance
  • Inbuilt input / bypass input / output / maintenance bypass breakers for completed distribution panel
  • Slim design and smallest footprint (40 kW in 0.15 m²) to reduce the space wasting
 

Low Total Cost of Ownership

  • Wide battery quantity configuration (30-46 pcs) to optimize the battery solution
  • High AC-AC efficiency over 96% and ECO mode to 99% resulting in marked energy cost savings
  • Low input harmonic distortion (iTHD < 2%) which is highly compatible with upstream of UPS power without additional filter or over sizing generator
 

High Manageability and Flexibility

  • User-friendly 5" color touch screen enables easy local UPS management
  • Optional SNMP IPv6 and Modbus communication cards for remote monitoring
  • Inbuilt 15 A charger for long backup solution without additional cost
  • Optional IP42 kit for harsh environment application
  • Front access and easy battery replacement for inbuilt battery models
Applications

UPS HPH Series applications

Specifications
  1. Model
  2. UPS:
    HPH-20K / HPH-30K / HPH-40K
  3. UPS Integrated Battery Model - Batteries Inside:
    HPH-20KB / HPH-30KB / HPH-40KB
  4. UPS Integrated Battery Model - No Batteries Inside:
    HPH-20KB-N / HPH-30KB-N / HPH-40KB-N

  5. Power Rating
  6. HPH-20K/B/B-N: 20 kVA / 20 kW
    HPH-30K/B/B-N: 30 kVA / 30 kW
    HPH-40K/B/B-N: 40 kVA / 40 kW

  7. Input
  8. Nominal Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
  9. Voltage Range: 305-478 Vac (full load), 228-305 Vac (with derating to 70-100%)
  10. Current Harmonic Distortion(1) :
    HPH-20K/B/B-N: ≤ 2.5%
    HPH-30K/B/B-N: ≤ 2%
    HPH-40K/B/B-N: ≤ 2%
  11. Power Factor: > 0.99
  12. Frequency Range: 40-70 Hz

  13. Output
  14. Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
  15. Voltage Harmonic Distortion
    ≤ 1.5% (linear load)
    ≤ 4% (non-linear load)
  16. Voltage Regulation: ± 1% (static)
  17. Frequency: 50/60 Hz
  18. Overload Capability
    ≤ 105%: continues
    > 105-≤ 110%: 60 mins
    > 110-≤ 125%: 10 mins
    > 125-≤ 150%: 1 min
    > 150%: 1 sec

  19. Display : 5” color touch screen

  20. Interface
  21. Standard
    External battery temperature detection x1, Output dry contact x4, Input dry contact x2, Parallel port x2, USB Port x1, RS232 Port x1, REPO Port x1, Mini Slot x2

  22. Conformance
  23. Safety: CE, RCM (IEC62040-1, IEC62040-2 Class C2)

  24. Efficiency
  25. AC-AC: > 96% (Peak efficiency)
  26. ECO Mode: 99%

  27. Battery
  28. Nominal Voltage: ± 240 Vdc (default, ± 180 Vdc(2) - ± 276 Vdc configurable)
  29. Charge Voltage: ± 272 Vdc (adjustable from 204 V to 312 V)
  30. Maximum Inbuilt Charger Current: 15 A
  31. Discharge Time(3)
    HPH-20K/B/B-N: 20 mins
    HPH-30K/B/B-N: 14 mins
    HPH-40K/B/B-N: 9.5 mins

  32. Environment
  33. Operating Temperature: 0 to 40 ℃
  34. Relative Humidity: 0~95% (non-condensing)
  35. Audible Noise (at one meter) :
    HPH-20K/B/B-N: < 50 dBA
    HPH-30K/B/B-N: < 56 dBA
    HPH-40K/B/B-N: < 56 dBA
  36. IP Protection: IP20 (Standard)

  37. Others
  38. Parallel Redundancy and Expansion: Up to 4 units
  39. Battery Start: Yes

  40. Physical
  41. Dimensions (W x D x H): 240 x 630 x 650 mm
  42. Weight
    HPH-20K: 44 kg
    HPH-30K/40K: 50 kg

  43. Physical (B/B-N)
  44. Dimensions (W x D x H): 410 x 780 x 1200 mm
  45. Weight (B: with batt.)
    HPH-20KB: 334 kg
    HPH-30KB/40KB: 340 kg
  46. Weight (B-N: without batt.)
    HPH-20KB-N: 94 kg
    HPH-30KB-N/40KB-N: 100 kg

  47. HPH-B: UPS integrated battery model has batteries inside.
    HPH-B-N: UPS integrated battery model has no batteries inside.
    (1) When input harmonic distortion is less than 1%.
    (2) 30-34 pcs required load derating
    (3) UPS at 70% load with internal battery strings.

    All specifications are subject to change without prior notice.
Options
  • Battery temperature compensation cable
  • Dust filter
  • IP42 kit for long backup model
  • EPO button kit
  • SNMP IPv6 card
  • Modbus card
  • Relay I/O card