Liquid-to-Liquid Coolant Distribution Unit (L2L CDU), 1500 kW

The increasing demand for high-performance computing and advanced GPUs highlights the limitations of aircooling. Delta's SuperCDU offers a superior alternative, providing effective separation of facility and secondary circuits as well as precise control over flow, pressure, temperature, and coolant quality. It excels in managing high-density thermal load, maximizing computing power while minimizing data center PUE. The SuperCDU ensures operational reliability by preventing condensation and guarantees quality with its stainless steel plumbing and coolant filtration. Embrace the future of high-performance computing with Delta’s SuperCDU!




Downloads (EN) Request a Quote

Product Introduction

Features & Benefits

Cost Effective

  • Maximize energy saving: cuts power consumption, surpassing traditional air cooling
  • Space optimization: compact design enables closer server placement further reducing Capex
  • Flexible integration: supports direct-to-chip and Rear Door Heat Exchanger (RDHx) application, adapting to existing setups and blending air and liquid cooling for future upgrades
 

High Reliability

  • Uninterrupted operation: dual power feed with ATS ensures continuous CDU operation
  • Optimized redundancy design ensures no single point of failure in the system
  • Leak detection: instant alarms with configurable response for efficient pumping action
  • Durable construction: stainless steel plumbing with 50-micron filters for long-term coolant quality
 

Easy Management

  • Intuitive interface: 10-inch color touchscreen displays real-time system status
  • Efficient control: group and manual control enhance system management and reliability
 
Specifications
  1. Model: SuperCDU-1500
  2. Nominal Cooling Capacity: 
    1500 kW @5°C approach, 1500 LPM secondary flow rate, 1500 LPM primary flow rate, 1.00 LPM/kW
    1377 kW @4°C approach, 1200 LPM secondary flow rate, 1200 LPM primary flow rate, 0.87 LPM/kW
    1210 kW @4°C approach, 1350 LPM secondary flow rate, 1200 LPM primary flow rate, 1.12 LPM/kW
    1170 kW @4°C approach, 1400 LPM secondary flow rate, 1200 LPM primary flow rate, 1.20 LPM/kW
    1035 kW @4°C approach, 1500 LPM secondary flow rate, 1200 LPM primary flow rate, 1.45 LPM/kW

  3. Primary Side
  4. Coolant Type: Water
  5. Nominal Coolant Flow Rate: 1200 LPM, 27°C primary inlet temperature
  6. Operation Pressure Drop: 13.5 psi @1200 LPM water flow rate
  7. Coolant Filter: 500μ with bypass to enable cleaning

  8. Secondary Side
  9. Coolant Type: 25%PG
  10. Nominal Coolant Flow Rate: 
    4x pumps: 1500 LPM @49.0 psi external pressure differential
    3x pumps: 1500 LPM @37.5 psi external pressure differential
  11. Approach Temperature: 5°C 
  12. Coolant Filter: 50μ redundant to enable cleaning
  13. External Pressure Drop: 49 psi

  14. Power Supply
  15. Nominal Power Supply Voltage: 380/400/415/480 Vac, 3P3W+PE
  16. Operating Voltage Range: 342-528 Vac
  17. Frequency: 50/60 Hz
  18. Maximum Over Current Protection (MOCP): 70 A
  19. Full Load Ampere (FLA): 54 A
  20. Dual Power Feed: Standard
  21. Power Feeds Location: Top

  22. Deployment
  23. Primary Connection: 4 in. sanitary ferrule
  24. Secondary Connection: 4 in. sanitary ferrule
  25. Primary and Secondary Connection Location: Top

  26. Physical
  27. Dimensions (W x D x H): 1200 x 1200 x 2300 mm
  28. Net Weight: 1900 kg (with coolant), 1600 kg (without coolant)

  29. Communication Interface
  30. Display: 10'' color touchscreen 
  31. Protocols: SNMP, Modbus TCP, Modbus RTU
  32. Monitoring
    Primary Side: Temp. (Inlet/Outlet), Flow, Pressure (Inlet, Filter ΔP)
    Secondary Side: Temp. (Supply/Return), Flow, Pressure (Supply, Return, Filter ΔP)
    Dew-point Temp.

  33. Conformance
  34. Safety: CE, UL/CSA 60335

  35. Features
  36. Leak Detection: Standard
  37. Pump Redundancy: 3x pump (N+1), 4x pump (N) run modes
  38. Temperature/Pressure Sensor Redundancy: Standard
  39. Integrated Variable Frequency Drivers (VFD’s): Standard
  40. Expansion Vessel Redundancy: 4x redundant 8L expansion vessels
  41. Auto-restart Function: Standard

  42. All specifications are subject to change without prior notice.