Introducing Delta RT Pro UPS, a top-tier high-performance online double-conversion solution featuring industry-leading AC-AC efficiency, unity power factor, and superior flexibility, all in a compact 2U size. Engineered to safeguard your critical applications from diverse power challenges, RT Pro ensures a resilient power foundation, paving the way for continuous business success and growth!

RT Pro 1-3 kVA UPS - LCD Panel




Downloads (EN) Request a Quote

Product Introduction

Features & Benefits

Power More from Less

  • Unity power factor (kVA=kW), provides maximum power for your facility
  • Industry leading AC-AC efficiency up to 94.3% and ECO mode efficiency up to 99% offer significant energy cost savings
  • Extends battery lifespan through reduced usage with wide 120-280V input range and a smart 3-stage battery charge mechanism
 

Superior Flexibility

  • Two programmable outlets group for power-cycling and optimize battery runtime for most critical applications
  • Easily scales for longer backup time with optional external battery pack
  • REPO/ ROO enables remote shutdown and restart during accidents to ensure safety
  • Integrated dry-contacts with user-selectable definition
  • Convertible rack and tower configuration with rotatable LCD screen
 

Easy Management

  • CE and UL certified, streamlines global models and service management for multinational operations
  • LCD display and intuitive interface offer effortless monitoring and configuration
  • Intelligent management software connectivity via RS-232, USB, or mini slot port for remote monitoring and setting
Applications

UPS RT Pro 1-3 kVA series UPS applications

Specifications
  1. Model
  2. RT Pro-1K / RT Pro-2K / RT Pro-3K

  3. Topology
  4. Online double-conversion

  5. Power Rating
  6. • RT Pro-1K: 1 kVA / 1 kW
    • RT Pro: 2 kVA / 2 kW
    • RT Pro: 3 kVA / 3 kW

  7. Input
  8. Nominal Voltage: 200/ 208/ 220/ 230/ 240 Vac, 1P2W+PE
  9. Voltage Range: 175-280 Vac (100% load), 120-175 Vac (with derating to 70-100% load)(1)
  10. Frequency: 40-70 Hz
  11. Power Factor: 0.99 (100% load)
  12. Connection
    • RT Pro-1K: IEC C14
    • RT Pro-2K/3K: IEC C20

  13. Output
  14. Nominal Voltage: 200(2)/ 208(2)/ 220/ 230/ 240 Vac, 1P2W+PE
  15. Voltage Regulation: ±3% (linear load)
  16. Frequency: 50/60 ± 0.05 Hz
  17. Total Harmonic Distortion (THDv): ≤ 2% (linear load)
  18. Power Factor: 1
  19. Connection
    • RT Pro-1K: IEC C13 ×2, Programmable IEC C13 ×2 ×2 groups
    • RT Pro-2K/3K: IEC C13 x2, IEC C19 x1, Programmable IEC C13 x2 x2 groups
  20. Overload Capability:
    < 105% continuous, 105-125%: 1 min ± 5 secs, 126-150%: 15 ± 3 secs, 151-155%: 0.1 secs
  21. Current Crest Ratio: 3:1

  22. Efficiency
  23. Online Mode: 
    • RT Pro-1K: 93.5%
    • RT Pro-2K: 94%
    • RT Pro-3K: 94.3%
  24. ECO Mode: 99%

  25. Battery
  26. Battery Type: VRLA
  27. Nominal Voltage
    • RT Pro-1K: 24 Vdc
    • RT Pro-2K: 48 Vdc
    • RT Pro-3K: 72 Vdc
  28. Quantity
    • RT Pro-1K: 2 pcs
    • RT Pro-2K: 4 pcs
    • RT Pro-3K: 6 pcs
  29. Charge Current: Up to 2.5 A

  30. Communication Interface
  31. Display: LCD display with LED indicators
  32. Port: USB, RS-232, REPO, Mini Slot, Input dry contact x1, Output dry contact x3
  33. REPO (Emergency Power Off): Standard 

  34. Physical
  35. Dimensions (W x D x H)
    • RT Pro-1K: 440 x 335 x 88 mm
    • RT Pro-2K: 440 x 430 x 88 mm
    • RT Pro-3K: 440 x 565 x 88 mm
  36. Net Weight
    • RT Pro-1K: 11.7 kg
    • RT Pro-2K: 21 kg
    • RT Pro-3K: 28 kg
  37. Packing Dimensions (W x D x H)
    • RT Pro-1K: 484 x 579 x 220 mm
    • RT Pro-2K: 594 x 508 x 220 mm
    • RT Pro-3K: 605 x 1005 x 220 mm
  38. Packing Weight
    • RT Pro-1K: 18 kg
    • RT Pro-2K: 28.8 kg
    • RT Pro-3K: 38 kg

  39. Environment
  40. Operating Temperature: 0 to 55°C(3)
  41. Humidity: 5-95% (non-condensing)
  42. Audible Noise(4): < 40 dBA
  43. Altitude: 0-3,000 m (derating 1%/100 m from 1,000-3,000 m)
  44. Ingress Protection: IP20

  45. Comformance
  46. Safety: CE, UL, cUL, RCM, UKCA
  47. EMC: IEC 62040-2
  48. Sustainability: RoHS, REACH

  49. (1) 200/ 208 Vac: 160-280 Vac (100% load); 120-160 Vac (with derating to 70-100% load)
    (2) Derating to 90% load
    (3) 40 to 50°C de-rating to 90% load; 50 to 55°C de-rating to 75% load
    (4) ECO mode at front side 1 meter
  50. All specifications are subject to change without prior notice.
     
Runtime Table
1 kVA
Load 100 W 200 W 300 W 400 W 500 W 600 W 700 W 800 W 900 W 1000 W
Internal Battery 70.3 31.9 18.4 11.9 8.2 6 4.6 3.6 2.9 2.4
UPS+1EBC 241.7 123 79.5 57 43.4 34.3 27.9 23.1 19.5 16.6
UPS+2EBC 414 215.7 142.6 104.7 81.6 66 54.9 46.5 40 34.8
UPS+3EBC 584.4 308.6 206.1 152.8 120.2 98.3 82.5 70.6 61.4 54
UPS+4EBC 758.8 401.6 269.7 201.1 159.1 130.8 110.4 95 83 73.4

2 kVA
Load 200 W 400 W 600 W 800 W 1000 W 1200 W 1400 W 1600 W 1800 W 2000 W
Internal Battery 73.6 33.6 19.5 12.6 8.8 6.4 4.9 3.8 3.1 2.5
UPS+1EBC 252.5 128.9 83.4 60 45.7 36.2 29.5 24.5 20.6 17.6
UPS+2EBC 432.3 225.8 149.5 109.9 85.7 69.4 57.7 49 42.2 36.8
UPS+3EBC 612.2 322.9 215.9 160.2 126.2 103.2 86.7 74.2 64.6 56.8
UPS+4EBC 792.1 420.1 282.4 210.7 166.8 137.2 115.9 99.8 87.2 77.2

3 kVA
Load 300 W 600 W 900 W 1200 W 1500 W 1800 W 2100 W 2400 W 2700 W 3000 W
Internal Battery 77 35.3 20.6 13.4 9.35 6.8 5.2 4.1 3.3 2.7
UPS+1EBC 263.6 134.9 87.5 63 48 38 31 25.8 21.8 18.6
UPS+2EBC 451 236.1 156.5 115.2 89.9 72.9 60.7 51.5 44.4 38.7
UPS+3EBC 638.5 337.5 225.9 167.8 132.2 108.2 90.9 77.9 67.8 59.7
UPS+4EBC 826.1 438.9 295.4 220.6 174.7 143.8 121.5 104.7 91.5 81
Unit: min