N Gen3 Series 1/2/3 kVA

Small and Reliable Power Guardian for Office & Home Critical Appliances

The Amplon N Gen3 Series 1-3 kVA is an online double-conversion uninterruptible power system (UPS) in a best-in-class compact size tower design. It supplies clean sine-wave input power for IT and other sensitive equipment and prevents work interruption, data loss or equipment damage from voltage sags, spikes, harmonic distortion and other power failures.

N Gen3 1-3kVA UPS - LCD Panel




Downloads:
English French German Italian Polish Spanish
Request a Quote

Product Introduction

Features & Benefits

High Availability

  • Output power factor 0.9 provides more wattage to critical loads
  • True online double-conversion topology and zero transfer time to battery mode
  • Generator compatibility ensures clean, uninterrupted power to the loads during an extended power outage
 

Green with Low TCO

  • Capable of working in harsh electrical environments with wide I/P voltage range to minimize battery usage
  • Excellent overload capacity allows the overload condition to continue within the timeframe
  • AC-AC efficiency up to 90%, and ECO mode efficiency up to 95% for better energy savings
 

Easy Management

  • The intuitive LCD display provides UPS status information with the ability to configure locally
  • Supports multiple communication interfaces, including USB port, RS-232 port and Mini slot (option for mini SNMP, mini Modbus and mini relay I/O card) for remote monitoring and configuration
  • Battery self-test function ensures early detection of the battery status when batteries need to be replaced
Applications

UPS N series applications

Specifications
  1. Model
  2. NX-1K / NX-2K / NX-3K

  3. Topology
  4. Online double-conversion

  5. Power Rating
  6. NX-1K: 1 kVA / 0.9 kW
    NX-2K: 2 kVA / 1.8 kW
    NX-3K: 3 kVA / 2.7 kW

  7. Input
  8. Nominal Voltage: 220/ 230 Vac, 1P2W+PE
  9. Voltage Range: 180-285 Vac (100% load), 120-180 Vac (60-100% load)
  10. Frequency: 40-70 Hz
  11. Power Factor: > 0.99 (100% load)
  12. Connection
    NX-1/2K: IEC C14
    NX-3K: IEC C20

  13. Output
  14. Nominal Voltage: 208(1)/ 220/ 230/ 240 Vac, 1P2W+PE
  15. Voltage Regulation: ±1%
  16. Frequency: 50/60 ± 3 Hz
  17. Total Harmonic Distortion (THDv): < 3% (linear load)
  18. Power Factor: 0.9
  19. Connection
    NX-1/2K: IEC C13 x4
    NX-3K: IEC C13 x4 + Terminal
  20. Overload Capability
    < 105%: continuous
    106-110%: 10 mins
    111-130%: 30 secs
    131-150%: 3 secs
    > 150%: immediately
  21. Current Crest Ratio: 3:1

  22. Efficiency
  23. Online Mode: Up to 90%
  24. ECO Mode: Up to 95%

  25. Battery
  26. Battery Type: VRLA
  27. Nominal Voltage
    NX-1K: 24 Vdc
    NX-2K: 48 Vdc
    NX-3K: 72 Vdc
  28. Quantity
    NX-1K: 2 pcs
    NX-2K: 4 pcs
    NX-3K: 6 pcs
  29. Runtime - 100% load
    NX-1K: 3.1 mins
    NX-2K: 3.3 mins
    NX-3K: 3.6 mins
  30. Runtime - 70% load
    NX-1K: 6.1 mins
    NX-2K: 6.5 mins
    NX-3K: 6.9 mins
  31. Charge Current: 1 A

  32. Communication Interface
  33. Display: LCD screen with LED indicators
  34. Port: USB, RS-232, Mini slot
  35. Audible Alarm: Battery mode, Low battery, Overload, Fault, Bypass mode

  36. Physical
  37. Dimensions (W x D x H)
    NX-1K: 145 x 282 x 220 mm
    NX-2K: 145 x 492 x 220 mm
    NX-3K: 190 x 421 x 318 mm
  38. Net Weight
    NX-1K: 9.2 kg
    NX-2K: 16.8 kg
    NX-3K: 27 kg
  39. Packing Dimensions (W x D x H)
    NX-1K: 230 x 360 x 325 mm
    NX-2K: 230 x 590 x 355 mm
    NX-3K: 320 x 560 x 460 mm
  40. Packing Weight
    NX-1K: 10.3 kg
    NX-2K: 18.6 kg
    NX-3K: 28.4 kg

  41. Environment
  42. Operating Temperature: 0 to 50 °C (40 to 50 °C de-rating to 70% load)
  43. Humidity: 20-90% (non-condensing)
  44. Audible Noise(2): < 45 dBA
  45. Altitude: 0-4,000 m (derating 1%/100 m from 1,000-4,000 m)
  46. Storage Temperature: -20 to 50°C
  47. Ingress Protection: IP20

  48. Conformance
  49. Safety: CE, UKCA
  50. EMC: IEC 62040-2
  51. Sustainability: RoHS, REACH

  52. (1) De-rating to 70% load
    (2) Audible noise test with UPS < 75% load at 25 °C in online mode
  53. All specifications are subject to change without prior notice.
     
Runtime Table
1 kVA
Load 90 W 180 W 270 W 360 W 450 W 540 W 630 W 720 W 810 W 900 W
Backup Time 57.5 26.9 16.8 11.9 9.1 7.3 6.1 4.3 3.6 3.1

2 kVA
Load 180 W 360 W 540 W 720 W 900 W 1080 W 1260 W 1440 W 1620 W 1800 W
Backup Time 61.1 28.3 17.7 12.5 9.5 7.7 6.5 4.5 3.8 3.3

3 kVA
Load 270 W 540 W 810 W 1080 W 1350 W 1620 W 1890 W 2160 W 2430 W 2700 W
Backup Time 67.1 29.4 18.1 12.5 10.3 8.2 6.9 4.9 4.2 3.6
Unit: min